OPERATION
BE3-37 and BE3-51 ac current relays have two external, user
adjustable controls marked SET and DELAY. The BE3-37/51 has
four controls: UNDER SET, UNDER DELAY, OVER SET, and
OVER DELAY. The SET control adjusts the relay trip point. An
overcurrent trip causes the relay output to energize when the
current rises above the SET threshold. The overcurrent SET level is
adjustable from 40 to 120% (±3%) of nominal input. An undercurrent
trip causes the relay output to de-energize when the current
decreases below the SET threshold. The undercurrent SET level is
adjustable from 0 to 80% (±3%) of nominal input. Time delay is the
amount of time that elapses after the trip point is reached and when
the output relay operates.
Setting Example
A BE3-51 relay has the following settings:
SET – 120%
DELAY – 4 seconds
A trip occurs when the sensing current rises above six amperes for
four seconds. Reset occurs when the current decreases below 5.75
amperes (5% of nominal below trip setting).