INTRODUCTION
Three-input BE3 temperature relays use resistance
temperature detectors (RTDs) to monitor remote
temperatures. When any of three monitored temperatures
exceeds a preset limit, the corresponding relay output
operates. A dc metering output indicates the highest
temperature of the three RTDs. BE3 temperature relays are
available for use with 10 Ω copper or 100 Ω platinum RTDs.
OPERATION
Three temperatures are monitored through RTDs connected
at the nine-position front panel connector. RTD connections
are labeled A, B, and C. Three user-adjustable controls are
located on the front panel: SET 1. SET 2. and SET 3. Each
setpoint is adjustable from 50 to 100% (±3%) of the RTD
temperature range. When a setpoint is exceeded, the
corresponding TRIP LED lights and the relay output
energizes. Each RTD has a corresponding LED to identify
which RTD has exceeded the temperature setpoint. For
example, if the temperature of RTDs B and C exceeds the
trip level, the B and C TRIP LEDs light and the relay output
energizes. A green LED labeled AUX indicates the power
supply status. Figure 1 illustrates the BE3-49R controls,
indicators, and terminals.