Operation
The FGD-2 continuously monitors the machine field circuit for ground faults.
Ground faults are detected through the measurement of leakage current to
ground which is determined by measuring the voltage drop across a shunt
resistor within the ground detector source. The Basler device connected to
the FGD-2 receives a voltage signal from the ground detection source that
is proportional to the level of field leakage current. The excitation
capabilities and analog input ranges of different Basler products will limit
the maximum compatible field voltage for accurate field ground resistance
measurements. Refer to Table 2 for more details.
AIOM-2
In a DECS-2100 system, the AIOM-2/AIOM digitizes the signal and transmits
it via fiber optic cables to the ECM-2. In an ECS2100 system, the digitized
signal is received by the ECM/SIM. The value of leakage current appears as
an input to the BESTCOMS™Pro FLDGND logic block. Within the FLDGND
logic block, a value of resistance to ground is calculated from the voltage
applied and the level of leakage current measured. Typically, this calculated
resistance value is transmitted to a display panel via the PMOUT logic block.
In the event of a low field ground resistance value, the FLDGND logic block
issues a Low Field Ground Resistance alarm. During detection of low field
ground resistance, an alarm issued by the DIGROUT logic block can be used
to energize a relay within the system’s Digital I/O Module (DIOM-2 or DIOM).
This annunciation may be used to provide a dry relay contact for a remote
alarm.