Functional Description
Introduction
The IFM-150 Interface Firing Module receives a control signal from the DECS-400 or DECS-450 Digital
Excitation Control System and then calculates a time delay based on the zero crossing of each phase of
voltage from the synchronizing transformer. At the end of the time delay, the IFM-150 produces the
properly synchronized sets of pulses to drive the SCRs of the excitation system rectifier chassis. As the
DECS control signal increases (or decreases), the time interval between the zero crossing of each phase
voltage and the start of its next output pulse will decrease (or increase). This results in an increase (or
decrease) in the rectifier chassis output voltage.
A terminal voltage limiter within the IFM-150 can be enabled to monitor the generator voltage through the
synchronizing transformer or external voltage transducer and compare the measurement with a user
adjustable reference level. If the generator voltage exceeds the reference level for a user-adjustable
amount of time, the IFM-150 will modify the SCR firing pulses and limit the generator voltage.
Inputs
The function of each IFM-150 input is described in the following paragraphs.