APPLICATION
BASIC PRINCIPLES
Differential relaying is the most selective form of fault
protection that may be applied to the individual
elements, or zones, of ac power systems. Various
types of differential relays and relaying systems have
evolved to take advantage of the differential principle.
The BE1-87G is a single or three-phase solid-state
variable percentage differential relay designed to
provide selective, high-speed differential protection
for generators, motors, and shunt reactors.
The selectivity of differential relaying is based on the
ability of the relay to distinguish between an internal
fault (within the protected zone) and an external fault.
Under normal operating conditions the current into
the protected zone equals the current out of the
protected zone with a net operating current equal to
zero. Internal faults upset this balance and result in a
difference between the input and output currents.
External faults have relatively little effect on the
balance, because the current in still equals the
current out of the protected zone. Therefore, by
comparing the currents on both sides of the protected
element or zone and detecting when these currents
are not equal, a differential relay acts to isolate the
element or zone from the system.
The BE1-87G typically trips a lockout relay (86), which
in turn trips the generator breaker and, when present,
the field and/or neutral breakers.