The EL2262 digital output terminal connects the binary control output

signals at the process level with electrical isolation. The outputs are

controlled with an adjustable integral multiple (oversampling factor: n)

of the bus cycle frequency (n microcycles per bus cycle).

For each bus cycle, the EtherCAT Terminal receives a process data block

that is output consecutively. The timebase of the terminal can be

synchronized precisely with other EtherCAT devices via distributed

clocks. An output pattern with a significantly higher pulse sequence

than the bus cycle time is thus output precisely with the system-wide

timebase. This procedure enables the temporal resolution of the digital

output signals to be increased to n times the bus cycle time.

The maximum output rate is 1 Msamples/s.

Special features:

• push-pull output

•connection of different load types possible (ohmic, inductive, lamp load)

•synchronized operation through distributed clocks XFC technology possible

•multiple sampling of a process data through oversampling