The EL2912 TwinSAFE component is a digital output terminal.
It has two fail-safe outputs with up to 2 A. The outputs are controlled
by a TwinSAFE Logic-capable component via FSoE.
The EL2912 has safety parameters to specifically adapt the functionality
to the respective safety requirements. Thus, for example, a test of the
outputs can be configured with fine granularity in order to be able to
detect cross-circuits among other things and to react appropriately.
In addition, standard outputs can be activated for the EL2912.
As a result, corresponding standard outputs are available in parallel
and internally ANDed with the safe outputs of the EL2912.
The safe output signals, which are controlled by a TwinSAFE Logic, thus
issue the safe release for the standard signals, which can then be
triggered by the non-safety oriented control system independently of the
cycle of the safety controller and FSoE. This allows faster switching times
of the outputs, provided that the safety controller issues the necessary
release for the output.