Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac RMS to chassis or instrument
ground for one minute with a leakage current not to exceed 25 mA, for all terminals to ground. Input
and output circuits are electrically isolated from each other, from other circuits, and from ground.
Surge Withstand Capability: All input and output circuits are protected against system transients.
Units pass all requirements of ANSI/IEEE C.37.90.1‑1989 defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against electromagnetic
radiated interference from portable communications transceivers.
Control Accuracy Specification: All units comply with ANSI/IEEE C57.15‑1986 defining control
accuracy of operation.
Environmental
Temperature Range: Functionality is maintained from ‑40° to +85° C.
Humidity: Functionality is maintained under 95% relative humidity (non‑condensing).
Fungus Resistance: A conformal printed circuit board coating inhibits fungus growth.