Interface
External connections are made to one terminal block, located on a separate
(provided) bracket which mounts within the existing enclosure.
Features
Fuse for voltage sensing is on the front panel. A spare fuse is provided within
the fuse housing.
AUTO/OFF/MANUAL switch.
Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac rms to
chassis or instrument ground for one minute with a leakage current not to
exceed 25 mA, for all terminals to ground. Input and output circuits are
electrically isolated from each other, from other circuits, and from ground.
Surge Withstand Capability: All input and output circuits are protected against
system transients. Units pass all requirements of ANSI/IEEE C.37.90.1-1989
defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against
electromagnetic radiated interference from portable communications transceivers
as outlined in ANSI/IEEE C37.90.2-1987 defining radiated electromagnetic
withstand capability.