Options

SCADA CUTOUT switch allows Local blocking of SCADA commands (for

use with SCADA enabled M‑2001C controls). The SCADA Cutout switch

must be used with a M-2001 Series Control with firmware version

D‑0146V08.01.22 or later installed.

SCAMPTM (AUTO/MANUAL) pushbutton switch allows the Auto/Manual

state on the adapter panel to be changed by a SCADA command.

The SCAMP pushbutton switch must be used with a M‑2001 Series Control

with firmware version D-0146V08.05.XX or later installed.

Voltage Reduction switch allows 2 levels of Voltage Reduction to be selected.

Testing Specifications

High Voltage: All input and output terminals will withstand 1500 Vac rms

to chassis or instrument ground for one minute with a leakage current not

to exceed 25 mA, for all terminals to ground. Input and output circuits

are electrically isolated from each other, from other circuits and from ground.

Surge Withstand Capability: All input and output circuits are protected against

system transients. Units pass all requirements of ANSI/IEEE C.37.90.1-1989

defining surge withstand capability.

Radiated Electromagnetic Withstand Capability: All units are protected

against electromagnetic radiated interference from portable communications

transceivers.

Environmental

Temperature Range: Functionality is maintained from -40° to +85° C.

Humidity: Functionality is maintained under 95% relative humidity (non-condensing).

Fungus Resistance: A conformal printed circuit board coating inhibits fungus growth.