Features

A shorting link for the line current output, a fuse for motor power, and a voltmeter testing terminal are included.

A DRAG-HANDS RESET button, LOWER/OFF/RAISE switch; and AUTO/MANUAL switches are also standard.

Options

SCADA CUTOUT switch allows Local blocking of SCADA commands (for use with SCADA enabled

M-2001C controls). Use of the SCADA Cutout switch requires an M‑2001 Series Control with firmware version

D‑0146V08.01.22 or later installed.

The Voltage Reduction switch allows 2 levels of Voltage Reduction to be selected.

Testing Specifications

High Voltage: All input and output terminals will withstand 1500 Vac rms to chassis or instrument ground for

one minute with a leakage current not to exceed 25 mA, for all terminals to ground. Input and output circuits

are electrically isolated from each other, from other circuits and from ground.

Surge Withstand Capability: All input and output circuits are protected against system transients. Units

pass all requirements of ANSI/IEEE C.37.90.1‑1989 defining surge withstand capability.

Radiated Electromagnetic Withstand Capability: All units are protected against electromagnetic radiated

interference from portable communications transceivers.