TESTING SPECIFICATIONS
• High Voltage: All input and output terminals will withstand 1500 Vac rms to
chassis or instrument ground for one minute with a leakage current not to
exceed 25 m.A, for all terminals to ground. Input and output circuits are
electrically isolated from each other, from other circuits and from ground.
• Surge Withstand Capability: All input and output circuits are protected against
system transients. Units pass all requirements of ANSI/IEEE C.37.90.1-1989
defining surge withstand capability.
• Radiated Electromagnetic Withstand Capability: All units are protected against
electromagnetic radiated interference from portable communications transceivers
as outlined in ANSI/IEEE C37.90.2-1987 defining radiated electromagnetic
withstand capability.
• Control Accuracy Specification: All units comply with ANSI/IEEE C57.15-1986
defining control accuracy of operation.
ENVIRONMENTAL
Temperature Range: Stated accuracies are maintained from -40° to +80° C.
Humidity: Stated accuracies are maintained under 95% relative humidity (non-
condensing). Fungus Resistance: A conformal printed circuit board coating inhibits
fungus growth.