• Available in four different Mounting configurations shown above, plus
Surface Mount (Option S1)
• Facilitates standardization for small/medium intertie and generator
protection applications
• Microprocessor-based relay provides 15 protective relay functions,
including Sync-Check, 2 programmable outputs and 2 programmable
inputs
• Relay voltage inputs can be directly connected (no VT required) for
voltages 480 V or less
• Local and remote serial communications (MODBUS protocol)
capability for monitoring and control functions
Sequence of Events
A total of 32 nonvolatile events can be stored. The recorded information
includes the function(s) operated, the function(s) picked up, input/output
contact status and time stamp. The events can be retrieved through the
communications port. After the 32nd event is stored, additional events
result in the oldest event being dropped (FIFO).
The information is time-stamped to 1 ms resolution.