Turn-on/off Battery Load Test Command
M‑2032B Battery Charger/Power Supply – Specification
The M‑7600 Series issues the “Turn‑on/off Battery Load Test” command to the
M‑2032B to test the battery capacity when the unit is operating from the main
power supply.
Turn-on/off 13.8 Vdc Accessory Supply (Aux Power)
The accessory supply provides power for external devices such as radio,
modems, etc. When the M‑2032B is used in conjunction with the M‑7600
Series, the 13.8 Vdc output can be enabled/disabled utilizing the control’s
HMI, IPScom, or communication protocols.
Turn Battery Supply Off Command
When the battery voltage decreases to less than a level set by the user, the
battery supply to the M‑7600 Series will be turned off (Sleep Mode) to protect
the battery. Discharging batteries below certain levels will shorten the life of
or damage the battery.
Wakeup System Command
The Wakeup system command is initiated by the M‑2032B local panel pushbutton.
The wakeup system command allows the user to wake the M‑7600 Series from
the Sleep Mode that was initiated by the Battery Supply Off command.
The wakeup system command restores power to the unit for a user defined time
period. If the main source power is not restored, then the Turn Battery Supply
Off command will be reinstated placing the M‑7600 Series in Sleep Mode.
Leave a comment