Welcome to the official website of CNIACS Automation Technology Co., Ltd!

ABB SIM4F Channel indication and metering functions

Channel indication and metering functions

SIM4F Sensor input module for fault channel indication using current information only

Intelligent Control Module SCM8H High voltage range,

four opto-isolated binary inputs, pair of two inputs with common loop

Pair of binary inputs and four fast power outputs for use in different motor control applications

Motor Control Applications

SCM8L Low voltage range, four opto-isolated binary inputs with common loop for

a pair of two inputs and four fast power outputs for different motor control applications

Pair of binary inputs and four fast power outputs for use in different motor control applications.

Digital output module DOM4 Four output contacts per digital output module,

two pairs of potential-free contacts with common loop

RTD4 RTD Module Four opto-isolated channels supporting RTD sensors

(Pt100. Pt250. Ni100. Ni120 and Ni250) and mA inputs (configurable 0…20 mA). .20 mA).

The channels are non-isolated from each other

Analogue Output Module AOM4 Four independently isolated and configurable mA output channels drive

0…. .20 mA.

ABB Digital Output Module DOM4

Digital Output Module DOM4

Digital output module DOM4 Four output contacts per digital output module,

two pairs of potential-free contacts with common loop

RTD4 RTD Module Four opto-isolated channels supporting RTD sensors

(Pt100. Pt250. Ni100. Ni120 and Ni250) and mA inputs (configurable 0…20 mA). .20 mA).

The channels are non-isolated from each other

Analogue Output Module AOM4 Four independently isolated and configurable mA output channels drive

0…. .20 mA.

Single channel

Sensor input module SIM8F Sensor input module with three-phase current and voltage combinations for

fault

Channel indication and metering functions

SIM4F Sensor input module for fault channel indication using current information only

Intelligent Control Module SCM8H High voltage range,

four opto-isolated binary inputs, pair of two inputs with common loop

Pair of binary inputs and four fast power outputs for use in different motor control applications

Motor Control Applications

SCM8L Low voltage range, four opto-isolated binary inputs with common loop for

a pair of two inputs and four fast power outputs for different motor control applications

Pair of binary inputs and four fast power outputs for use in different motor control applications

ABB Remote I/O RIO600 Product Guide Communication

Communication

RIO600 supports the horizontal GOOSE

communication of the IEC 61850 substation

automation standard.

RIO600 is designed to send and receive binary

signals to or from the ABB Relion® series IEDs

and the station automation device COM600 using

the IEC 61850-8-1 GOOSE (Generic Object

Oriented Substation Event) profile.

RIO600 communication module includes a

galvanic Ethernet RJ-45 port for IEC 61850

GOOSE communication. The used cable type

must be at least Shielded Twisted Pair (STP) CAT5e.

Using the same Ethernet port, RIO600 can be

connected in parallel to PCM600 and a Web

browser over the same communication bus.

Indication LEDs

RIO600 is equipped with different indication LEDs

available on different modules.

•Ready LED on all modules

•Status indication LED for each binary input and output

•Communication diagnostic LED on the communication module

ABB AIS885 Features and benefits

Features and benefits

• Analog input for 2-wire, 3-wire or 4-wire field devices, powered by AIS885

• Signal range: 4…20 mA

• Can be used in hazardous areas

• Certified for Functional safety

• Field power sourced from the power injection

• Short circuit proof, configurable current limit 0.1 to 1.2 A

• Transmitter power current limited to 25 mA (for 2-wire field devices; input current limitation for

SCM pin 2)

• 16 bit A/D converter resolution

• Galvanic isolation

• Protected against wrong wiring (±35 V) between all terminals

• Hardware filter, rise time 1 ms

• Software filter configurable through parameters

• Diagnostics:

– Loop supervision (open circuit and short circuit)

– Internal hardware supervision

– Communication supervision

– Device malfunction low, under range, over range and device malfunction high detection

– Internal power supervision

– Power injection supervision

• LED indicators:

– Status (S)

– Primary (P)

• Single loop granularity – each SCM handles a single channel

• Supports hot swap

• Mechanical locking slider which turns off field device power and/or output before removal

• Field disconnect function which can galvanically separate the field loop wiring from the SCM during

commissioning and maintenance

• All SCMs have electronic current limitation

• Mechanical keying to prevent insertion of wrong module type after commissioning

• 24V DC powered through Modulebus

• Configurable through parameters

• LED indicators on the SCM indicate the operational state of the module.

ABB AIS885 Ability™ System 800xA® hardware selector

Select I/O is an Ethernet networked, single-channel granular I/O

system for the ABB Ability™ System 800xA automation platform.

Select I/O helps decouple project tasks, minimizes the impact of

late changes, and supports standardization of I/O cabinetry

ensuring automation projects are delivered on time and under

budget. A Signal Conditioning Module (SCM) performs the

necessary signal conditioning and powering of the connected field

device for one I/O channel.

The AIS885 is an Analog Input Signal Conditioning Module (16-bit)

for use in High Integrity applications (certified for SIL3) supporting

2/3/4-wire devices (1.2 amp) and HART communications.

ABB DIS801 Features and benefits

Features and benefits

• Digital input for 2-wire, 3-wire and externally powered 4-wire field devices

• Can be used in hazardous areas

• Field device power output current limited to 35 mA

• Channel to channel galvanic isolation

• Configurable software signal filter 0…100 ms

• Protected against wrong wiring

• Diagnostics:

– Loop supervision (open circuit and short circuit)

– Communication supervision

– Internal power supervision

• Sequence of Events (SoE)

• DIS801 supports both Normally Open (NO) and Normally Closed (NC) 24 V loops

• Single loop granularity – each SCM handles a single channel

• Supports hot swap

• Mechanical locking slider which turns off field device power and/or output before removal

• Field disconnect function which can galvanically separate the field loop wiring from the SCM during

commissioning and maintenance

• All SCMs have electronic current limitation

• Mechanical keying to prevent insertion of wrong module type after commissioning

• 24V DC powered through Modulebus

• Configurable through parameters

• LED indicators on the SCM indicate the operational state of the module

ABB DIS801 Ability™ System 800xA® hardware selector

Select I/O is an Ethernet networked, single channel granular I/O

system for the ABB Ability™ System 800xA automation platform.

Select I/O helps decouple project tasks, minimizes the impact of

late changes, and supports standardization of I/O cabinetry

ensuring automation projects are delivered on time and under

budget. A Signal Conditioning Module (SCM) performs the

necessary signal conditioning and powering of the connected field

device for one I/O channel.

The DIS801 is a Digital Input 24 V Signal Conditioning Module

supporting 2/3/4-wire devices with Sequence of Events (SOE).

ABB CI854B Ability™ System 800xA® hardware selector

PROFIBUS DP is a high speed multipurpose bus protocol (up to

12Mbit/s) for interconnecting field devices, like remote I/O,

drives, low voltage electrical equipment, and controllers.

PROFIBUS DP can be connected to the AC 800M via the CI854B

communication interface. The CI854B includes two PROFIBUS

ports to realize line redundancy and it also supports PROFIBUS

master redundancy.

Master redundancy is supported in PROFIBUS-DP communication

by using two CI854B communication interface modules. The

master redundancy can be combined with CPU redundancy and

CEXbus redundancy (BC810). The modules are mounted on a DIN

rail and interface directly with the S800 I/O system, and other I/O

systems as well, including all PROFIBUS DP/DP-V1 and

FOUNDATION Fieldbus proficient systems.

The PROFIBUS DP must be terminated at the two outermost

nodes. This is usually done by using connectors with built-in

termination. To guarantee a correct working termination the

connector has to be plugged and power supplied.

Package including: a CI854BK01 Communication Interface and a

TP854 Baseplate.

ABB CI854B Features and benefits

Features and benefits

• Used for connecting remote I/O and fieldbus instruments via PROFIBUS DP

• Possible to connect PROFIBUS PA to the CI854B via the PROFIBUS linking device LD 800P

• The CI854B can be set redundant

PROFIBUS DP is a high speed multipurpose bus protocol (up to

12Mbit/s) for interconnecting field devices, like remote I/O,

drives, low voltage electrical equipment, and controllers.

PROFIBUS DP can be connected to the AC 800M via the CI854B

communication interface. The CI854B includes two PROFIBUS

ports to realize line redundancy and it also supports PROFIBUS

master redundancy.

Master redundancy is supported in PROFIBUS-DP communication

by using two CI854B communication interface modules. The

master redundancy can be combined with CPU redundancy and

CEXbus redundancy (BC810). The modules are mounted on a DIN

rail and interface directly with the S800 I/O system, and other I/O

systems as well, including all PROFIBUS DP/DP-V1 and

FOUNDATION Fieldbus proficient systems.

CI857 ABB Ability™ System 800xA® hardware selector

Features and benefits

• Maximum number of MCUs (or other INSUM devices) per AC 800M: – 256 MCUs (or other INSUM

devices) per AC 800M with PM864 or PM866. – 128 MCUs (or other INSUM devices) per AC 800M

with PM861.

• Maximum 6 CI857 per AC 800M.

• Maximum 128 MCUs (or other INSUM devices) per CI857.

• Maximum 2 INSUM TCP/IP Gateways per CI857.

• Maximum 128 INSUM devices per INSUM TCP/IP gateway.

• Four LonWorks subnets per INSUM TCP/IP gateway.

• Maximum 32 devices per LonWorks subnet.

INSUM integration into AC 800M supports higher functionality

integration, multidrop configurations, time distribution and time

stamping in the switchgear, and utilizes standard Ethernet

technology for longer communication distances. The speed of this

solution is typically 500 ms for one closed loop (indication from

one motor until operation of another, assuming 250 ms cycle time

in control execution).

AC 800M controllers access the INSUM functions through function

blocks in the INSUM Communication Library. The CI857 is powered

by the processor unit, via the CEX-Bus, and therefore does not

require any additional external power source.

Search for products

Back to Top
Product has been added to your cart