ABB Relion® Protection and Control REX640 Trip circuit supervision
Trip circuit supervision
The trip circuit supervision continuously monitors the availability
and operability of the trip circuit. It provides open-circuit
monitoring both when the circuit breaker is in closed and in
open position. It also detects loss of circuit-breaker control voltage.
Self-supervision
The relay’s built-in self-supervision system continuously
monitors the state of the relay hardware and the operation of
the relay software. Any fault or malfunction detected is used for
alerting the operator.
A permanent relay fault blocks the protection functions to
prevent incorrect operation.
The load profile recorder stores the historical load data
captured periodically (demand interval). Up to 12 load
quantities can be selected for recording and storing in the
nonvolatile memory. The recordable quantities include
currents, voltages, power and power factor values. The
recording time depends on a settable demand interval
parameter and the amount of quantities selected. The
quantities’ type and amount to be recorded are determined in
the application configuration. The recorded quantities are
stored in the COMTRADE format.