Beckwith Electric M-0067E Modes of Operation
Modes of Operation
Either of the following modes are available as determined by the presence or absence of a cam switch which
is closed while the LTC is in transition.
Non‑Sequential Mode: The timer resets after a tapchange, regardless of voltage.
Sequential Mode: The timer resets only after the sensed voltage is back within the control band.
LED Indicators
The RAISE and LOWER LEDs light to indicate a voltage outside the band and a forthcoming tapchanger
operation as soon as the timer times out. With a slowly varying input, operation of the LEDs and initiation of
timing is very sharp with 0.2 V hysteresis. The LEDs have an expected life of 25 years.
Output Contacts
Two outputs drive a raise and lower motor starter relay. The starters may be any voltage up to 240 Vac. The
output contacts are rated at 2.5 A inrush current and will handle a NEMA size 1 starter or smaller.
Voltage Measurement Accuracy
The unit meets the requirements of accuracy Class 1 as defined in ANSI standards C57.12.30‑1977 paragraph
9.3 and C57.15‑4.2 when tested according to C57.15‑1986 paragraph 9.4.1.