The M60 RTD option provides 8 programmable RTD inputs

Under/Over Frequency Protection

The under/over frequency protection

element detects when the motor is

operating at off-nominal frequencies

(which can damage the process) or signals

to upstream protection or control to

implement load-shedding actions.

RTD Protection (Module Option 5C)

The M60 RTD option provides 8

programmable RTD inputs per module that

are used for monitoring the stator, bearing

and ambient temperatures. Each RTD input

has 2 operational levels: alarm and trip. The

M60 supports RTD trip voting and provides

open RTD failure alarming. Alternatively,

a remote RTD module “RRTD”, which

supports 12 RTD inputs, can also be used

with the M60 for temperature monitoring.

The RRTD provides cost savings compared

with standard RTD wiring.

Multilin™ M60 Under/Over Frequency Protection

Undercurrent Protection

The undercurrent protection element

provides the ability to trip the motor due

to external conditions that can cause the

load being pulled by the motor to drop

below a preset level.  This element is useful

when the loss of the load results in a loss

of cooling which will cause the asset to

overheat.

Under/Over Frequency Protection

The under/over frequency protection

element detects when the motor is

operating at off-nominal frequencies

(which can damage the process) or signals

to upstream protection or control to

implement load-shedding actions.

RTD Protection (Module Option 5C)

The M60 RTD option provides 8

programmable RTD inputs per module that

are used for monitoring the stator, bearing

and ambient temperatures. Each RTD input

has 2 operational levels: alarm and trip. The

M60 supports RTD trip voting and provides

open RTD failure alarming. Alternatively,

a remote RTD module “RRTD”, which

supports 12 RTD inputs, can also be used

with the M60 for temperature monitoring.

The RRTD provides cost savings compared

with standard RTD wiring.

The start inhibit function prevents the starting of a motor

Start Inhibit

The start inhibit function prevents the

starting of a motor when the motor is too

hot and does not have a sufficient amount

of thermal capacity available to allow a

start without being tripped offline.

Breaker Failure Protection

The breaker failure protection element

monitors for timely operation of the

connected breaker. If a trip command is

not successful in operating the breaker

and clearing the fault, the breaker failure

element can be used to send trip signals to

upstream breakers to clear the fault.

Undercurrent Protection

The undercurrent protection element

provides the ability to trip the motor due

to external conditions that can cause the

load being pulled by the motor to drop

below a preset level.  This element is useful

when the loss of the load results in a loss

of cooling which will cause the asset to

overheat.

Multilin™ M60 Motor protection system Acceleration Time

Mechanical Jam

The mechanical jam element senses

increased loading associated with

process or load related faults such as an

overloaded conveyor. A programmable

delay setting can be used to allow the

process to attempt to clear itself before

issuing a trip.

Acceleration Time

The M60 protects the motor from

overheating in cases of abnormal

loading during motor starts. The motor

can be tripped if the motor does not

reach a running condition within the

programmable motor acceleration time.

Stator Differential

The M60 provides stator differential

protection for fast clearing of stator phase

faults. Advanced CT saturation detection

algorithms and dual-slope characteristics

are incorporated for increased security

during heavy faults.

Short Circuit Protection

Short circuit overcurrent protection

protects damage to the motor during a

locked rotor condition. The M60 comes

with up to 8 instantaneous overcurrent

elements that can be configured for

protection, alarming, and control during

locked rotor conditions.

The M60 motor protection system offers comprehensive protection and control solutions

Protection and Control

The M60 motor protection system offers

comprehensive protection and control

solutions for medium to large-sized

three-phase motors.  The M60 includes

advanced automation and communication

capabilities, extensive I/O options, and

powerful fault recording features that can

simplify postmortem fault analysis and

help minimize motor downtime. As part

of the Universal Relay (UR) family, the M60

provides superior protection and control

that includes:

Motor Thermal Model

The M60 features an enhanced motor

thermal model consisting of the following

elements:

• Thermal limit curves – NEMA standard,

voltage dependent and customized

• IEC 60255-8 thermal overload curves

• Current unbalance biasing

• Independent running and stopped

exponential cooling curves

• Optional RTD biasing of the thermal

model to adapt to real-time

temperature measurements

• Compensation for hot/cold motor

conditions

The M60 thermal model integrates both

stator and rotor heating and cooling into

a single model.

FlexCurves™

For applications that require greater

flexibility, FlexCurves can be used to define

custom curve shapes. These curves can

be used to protect motors with different

rotor and stator damage curves, allowing

complete protection over the total motor

capacity.

Overtemperature Protection

The M60 supports up to 16 programmable

RTD inputs that allow for the configuration

of the alarm and trip temperature of each

RTD, detecting RTD shorting conditions,

and selecting RTD voting that requires

more than one RTD to detect an over

temperature condition before it will issue a

trip command.

IEC 61850 Process Bus Interface

Communications

• Networking interfaces: up to three Ethernet ports 100Mb fiber or

copper, RS485. RS232. RS422. G.703. C37.94

• Multiple protocols: IEC 61850. DNP 3.0 and Modbus® serial/TCP,

IEEE 1588. IEC 60870-5-104 and 103. PRP, SNTP, HTTP, TFTP, EGD

• DeviceNet and Profibus protocol options available using the D485

and P485 protocol convertors

• Direct I/O: secure, high-speed exchange of data between URs for

direct transfer trip (DTT) applications

IEC 61850 Process Bus Interface

• Robust communications with up to 8 HardFiber Bricks

• Redundant architecture for dependability and security

EnerVista Software

• Graphical Logic Designer and Logic Monitor to simplify designing

and testing procedures via EnerVista UR Engineer

• Service and update notification toolset ensures device documents

and software are up-to-date via EnerVista Launchpad

• EnerVista Integrator providing easy integration of data in the M60

into new or existing monitoring and control systems

Multilin™ M60 Motor protection system

APPLICATIONS

• Protection and control of most popular construction type

medium to large thee-phase induction motors

• Automation or process control functionality

• Protection of medium to large synchronous motors when paired

with the SPM Synchronous Motor Protection System

• Stand-alone protection or component in automated substation

control system

FEATURES

Protection and Control

• Enhanced thermal model with RTD and current unbalance

compensation

• Stator differential

• Mechanical jam/stall

• Short circuit tripping

• Under current/under power

• Phase reversal

• Reverse/low forward power protection

• Two-speed motor protection

• Reduced voltage starting

• Optional internal RTDs & external RTD module

• CT failure for each CT bank, VT fuse failure

Monitoring and Metering

• Metering: current, voltage, power, energy, frequency

• Advanced recording capabilities deliver a 1024 event recorder,

configurable and extended waveform capture and data logger

• Setting for security audit trails for tracking changes to M60

configurations

• Motor starting characteristics for the last 250 motor starts

GE Comprehensive Protection for Medium to Large Motors

Comprehensive Protection for Medium to Large Motors

KEY BENEFITS

• Advanced motor protection and control elements including a

flexible and powerful thermal model and standard, custom and

voltage dependant overload curves

• Integrated automation and process control functions

• Simplified programming with the EnerVista™ M60 motor settings

auto-configurator

• Three independent fiber or copper Ethernet ports for simultaneous/

dedicated network connections with 1 microsecond time

synchronization via LAN with IEEE® 1588 support

•  Reduced relay-to-relay wiring and associated installation costs

through high-speed inter-relay communications

• Increase network availability by reducing failover time to zero

through IEC® 62439-3 “PRP” support

• CyberSentry™ provides high-end cyber security aligned to industry

standards and services (NERC® CIP, AAA, Radius, RBAC, Syslog)

• Robust network security enabling Critical Infrastructure

Protection through user command logging, and dual permission

access control

• High-end fault and disturbance recording

• Enhanced motor-learned data provides critical information for

preventative maintenance

• Complete IEC 61850 Process Bus solution provides resource

optimization and minimizes total P&C life cycle costs

Maintain monitoring and control functionality of integrated Modbus devices

Key Benefits

• Integrate GE relays, meters or other Modbus-compliant devices into DeviceNet networks

• Maintain monitoring and control functionality of integrated Modbus devices in a DeviceNet network

• Easy-to-use, PC-based Enervista Setup Software for simple configuration

• Integrate your protection and automation systems into one network

Communications

The D485 Modbus to DeviceNet Converter acts as

a gateway between a Modbus RTU network and a

DeviceNet network. Integration of Modbus devices

into DeviceNet networks is enabled without loss

of functionality, control, and reliability, both when

retrofitting to existing equipment as well as when

setting up new installations. The D485 Modbus

to DeviceNet Converter is an external DIN-rail

mounted device which provides DeviceNet

network connectivity via a serial RS232/RS422/

RS485 interface. The D485 is programmed using

the P485/D485 configuration cable and the

EnerVista P485/D485 Setup Software.

The D485 Modbus to DeviceNet Converter acts

Connectivities

• Connects up to 10 Modbus devices to a DeviceNet network

• Contains pre-configured memory maps for specific GE Multilin devices

• Supports DeviceNet “Adapter” functionality (Profile Number 12)

• Supports Explicit and all four types of I/O

messaging formats:- Polled- Change of State (COS) – Bit strobed – Cyclic

• Supports DeviceNet baud rates 125 Kbps, 250 Kbps and 500 Kbps

• Connects to DeviceNet network using 5-pin linear DeviceNet plug

• Acts as a master to Modbus RTU devices

• Supports Modbus baud rate of 1200bps to 57600bps

• Modbus interfaces supported: RS232. RS422 RS485

• Supports up to 50 Modbus Transactions

• DIN-rail mountable

• 1024 bytes of total data exchange- 512 bytes of data to Modbus devices- 512 bytes of data to

DeviceNet master

• Configured using the EnerVista P485/D485 Setup Software

• Upload common configuration files to

multiple D485 devices

• 24 VDC input power

• CE, UL and cUL certified