560CVD11 Multimeter with FCD, 4U/4I

Can be set to automatically change the screen of the measurement page every 6 seconds and to display each screen once.

CT/VT interface with 3 voltage and 3 current inputs for direct monitoring of 3-wire 85…. .400 VAC

1 A/5 A input for AC transformers

RTU500 serial interface (RS-485)

Display on the front

Applications

The multimeter 560CVD11 is used to measure analog AC input signals from three independent phases with additional inputs for neutral current and voltage.

The module measures the voltage and current per www.cniacs.com phase directly and generates a series of calculated values.

In addition, the module can detect fault currents and the direction of overcurrent. The modules support configurations with 3 or 4 voltage transformers.

Features

The multimeter is a microprocessor-based intelligent electronic device (IED) for measuring current, voltage, power and energy.

Fault current detection and overcurrent indication are also provided.

The current and voltage inputs are connected via transformers only (see Wiring). The modules support configurations with 3 or 4 voltage transformers and 3 or 4 current transformers.

The calculated values are scaled according to the constants programmed by the user for the current and voltage transformers. All values are updated after 200 ms.

Fault current can be measured up to 20 times the rated current.

The current input can withstand 50 times the rated current for 1 second.

The multimeter is equipped with two binary outputs, which are not supported in the RTU500 series configuration.