Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Autronica Fire and gas alarm control panel BS-420G

Description / Application

BS-420 is a complete fire alarm control panel with full

operation capabilities. The panel serves as an operating

panel for one or several defined operation zones. All

alarm handling and system features can be controlled

and monitored from the panel.

The panel can accommodate up to a maximum of 12

modules. The system offers Loop Driver Modules for

detection loops and several types of I/O modules (see

Optional Modules below).

There can be a maximum of 6 Loop Driver Modules in

each panel. All modules are easily plugged onto each

other on a standard mounting rail inside the unit.

The panel provides connections for 2 Ethernet ports and

2 USB host ports.

The panel is menu operated on a 16-line display, with 40

characters per line. A printer is available as an option.

The panel communicates with other system units on the

Ethernet-based local area network, AutroNet.

Autronica BS-420G Features

Features

• SelfVerify function for automatic testing of detectors

• Automatic addressing of detectors

• AutroFieldBus

• Accommodates up to a maximum of 12 modules, of

which maximum 6 can be Loop Driver Modules

• User-friendly display and operator controls

• Backlit operational buttons. Text display suitable for

full darkness operation

• Surface mounting on wall

• Rack mounting in standard 19’’ cabinets

• Conforms to applicable EU directives and regulations

• SIL2 capable according to IEC 61508

• Approved according to CEN Standards EN 54-2.

EN 54-4 and EN 54-13. FM regulations (Factory

Mutual) and maritime regulations (IMO/SOLAS and

USCG)

Autronica System Design and Engineering AutroSafe Interactive Fire & Gas Detection System (IFG)

The figure below shows an example of a typical AutroSafe Integrated

Fire & Gas system:

 Fully integrated PowerLoop detectors are connected to the two

wire PowerLoop, no additional interfaces are required.

 Any 4-20mA devices can be connected to the system’s PowerLoop

by means of the BN-342 4-20mA interface. No additional power

supply is required, the PowerLoop will supply both the BN-342

module as well as the detector attached to it.

 Advanced Open Path Gas Detectors connected to the BN-342 4

20 mA interface provides the highest level of detection

performance. Including, but not limited to false alarm immunity,

logging and trending of analogue detector readings.

 The smoke- and heat detectors on the Al_Com loop employ the

DYFI+ technology, a dynamic filtering system which virtually

eliminates false alarms and provides the earliest possible warning

of a potential fire. A single pair of wires that provides both power to

– as well as interactive communication with – the detectors,

connects detectors, manual call points and interfaces. The Al_Com

loop also features the SelfVerify function, testing the detectors to

the calibrated set point every 24hours.

 Automatic addressing of detectors – No switch settings required.

For a detailed general description of the AutroSafe SelfVerify™

Integrated Fire and Gas System, please refer to Chapter 4.4.

Autronica AutroSafe Self Verify™ Integrated Fire

Brief Introduction

The AutroSafe Self Verify™ Integrated Fire and Gas detection system

described in key words is as follows:

 Both the Fire Detectors as well as the Gas Detectors can be

connected to the same panel or system.

 All detectors are interactive addressable devices with intelligent

communication. Non-addressable detectors can be connected via

a 4-20mA interface.

 Field devices have a built-in calibrated self-test to verify and

confirm their ability to perform correctly. This can be considered as

supplemental to – and can be used instead of – manual testing and

inspection routines. Refer to Chapter 4.4.

 Flame and Gas Detectors can be connected to the AutroSafe

Panel by using a 2-wire loop structure (PowerLoop). The

PowerLoop provides both power to, as well as interactive

communication with the detectors. Studies have shown that the

Fire & Gas Detection Control System’s cable requirement can be

reduced with 30-60% by utilizing this concept as opposed to

conventional systems.

 AutroSafe SelfVerify™ IFG is a modular and distributed system

providing maximum flexibility. The AutroNet communication

facilitates the possibility to link cause and effect across panels

within the same AutroNet. In other words, any detector connected

to any panel can activate any output associated to any panel. Each

panel can have up to 12 custom AutroSafe I/O modules. Within the

limitations of the system, the system designer can freely select the

type and number of modules to be used.

 There are a number of versatile communication options available:

 Physical: Ethernet, RS-232. RS-422. RS-485. Al_Com loop,

AutroFieldBus, PowerLoop and either hardwired or fibre-optic

based AutroNet (Ethernet).

 Protocols: Modbus RTU Slave or Master, Modbus TCP/IP

Slave or Master, ESPA 4.4.4. and AutroCom (Autronica’s

proprietary protocol).

Autronica AutroSafe 4 integrated fire and gas (IFG) panels

Our IEC 61508 SIL 2 approved system for the offshore industry.

The AutroSafe Integrated Fire and Gas (IFG) 4 is designed for the toughest

requirements and expands the possibilities of a F&G detection system even

further. From offshore platforms to LNG plants to refineries, AutroSafe IFG

delivers the most rigorous F&G safety yet.

Autronica Fire and Security launched AutroSafe, our high-end fire detection

system, in 1999. From day one, AutroSafe has proven its unique stability

and reliability in more than 15 000 of installations worldwide, both on- and

offshore. AutroSafe IFG 4 provides advanced functionality for a wide range

of applications. The system is designed to meet all requirements in the

high-end segment of the offshore market. It is certified according to European

directives (CPD) requiring EN 54 compliance, and is approved by Factory Mutual

(FM) according to NFPA 72. Additionally, the F&G system is approved according

to SIL2 requirements by TÜV Nord.

Reliable communication is paramount to your safety. That’s why we’re adding

AutroNet to the AutroSafe IFG system, an innovative network solution safeguarding

communication between panels. AutroNet ensures a redundant and high-speed

network, expanding the reach of the AutroSafe IFG system even further.

The system can be set up either in a star or ring network, depending on your needs.

History proves you can rely on AutroSafe IFG. All existing functionality has stood up

to the toughest tests worldwide for more than 10 years. With AutroSafe IFG 4.

Autronica has once again taken fire safety to a higher level.

Autronica AutroSafe Interactive Fire Detection System

AutroSafe 4 panels

AutroSafe is our high-end fire detection system for large and complex buildings.

Since the launch in 1999. it has proven its unique stability and reliability in more

than 15 000 installations worldwide, from hotels to cruise ships to drilling platforms.

AutroSafe 4 provides advanced functionality for a wide range of applications.

The system is designed to meet all requirements in the high-end segment of the

onshore, maritime and offshore market, and is certified according to Marine

Equipment Directive (MED) for Wheel marking, Construction Products Directive

(CPD) for CE marking, both requiring EN 54-2 and 4 compliance, and Factory

Mutual (FM) approval according to NFPA 72.

Reliable communication is paramount to your safety. That’s why we have added

AutroNet to the AutroSafe system, an innovative network solution safeguarding

communication between panels. AutroNet ensures a redundant and high-speed

network expanding the reach of the AutroSafe system even further.

The system can be set up either in a star or ring network, depending on your needs.

A maximum of 64 system units (panels, controllers) can be connected to the AutroNet.

The system has a great capacity, and the fact that all types of loop units can be

connected to the same detection loop gives large flexibility. Uploading of configuration

data or system software to the entire system can be done from one single point.

The USB port is used for downloading data from a USB memory stick.

Autronica POWER CABINET BP-405

Description/Application

The Power Cabinet BP-405 provides space for two

12V/18Ah batteries (not included).

The maximum power available is 24V/5A.

NOTE:

Do not connect batteries in parallel in an attempt to

obtain higher ampere hour (Ah) capacity.

If additional power is required in an installation, an

additional cabinet BP-405 with 24V/5A power supply

can be used.

The power supply and battery brackets are already

mounted when the cabinet is delivered from the

factory.

Dipswitch Settings

Dipswitch settings for dipswitch S6 on Power Board

BSF-400.

Autronica BP-405 Features

Features

 Power Cabinet containing 5A/24V power supply

and Power Board BSF-400 with 2x12V, 18Ah

batteries (batteries not included)

 Power Board BSF-400. including

 AutroFieldBus interface

 115VAC /230VAC input

 6 outputs 24VDC (max. 2A each)

 1 fault relay output

 Available space for 2x12V, 18Ah batteries

 Conforms to CE standards

 Designed to meet IEC 61508 SIL2 requirements,

CEN, EN 54-2. EN 54-4 and EN 54-13

regulations, FM regulations (Factory Mutual) and

the maritime SOLAS requirements (Safety Of

Life At Sea)

Autronica Fireman panel microphone kit

The Fireman Panel Microphone kit consists of an AutroSafe Fire Brigade

Panel BU-BV-420 and a miniVES/MULTIVES Fireman Microphone with zone

buttons in the same housing.

The AutroSafe Fire Brigade Panel is placed in the upper section of the kit. It is intended to provide information

related to fire alarms in the relevant Operation Zone and allow the fire brigade to operate fire alarms.

The panel displays alarms and allows you to operate alarms and receive additional information related to the

relevant operation zone. To operate alarms, a fireman’s key must be used (access level 2).

The panel is used to silence sounders and to reset alarms within a defined operation zone.

The panel provides the following buttons:

 More Events button

 Mute Panel button

 Silence Alarms button

 Reset System button

The panels provides the following indicators:

 Fire, More Events, Fire Brig. Signalled, Fault, Function Disabled, Testing, System Fault, Power

 Internal buzzer

For more detailed information about the Fire Brigade Panel, see separate datasheet (116-P-BU-BV-420/CGB).

Autronica Fire brigade loop panel BU-110

Description / Application

The unit has been designed for use with AutroSafe 4

Interactive Fire Detection System.

From the Fire Brigade Loop Panel BU-110 it is possible to

mute the panel’s internal buzzer, silence/resound

sounders/bells etc. and reset the system.

The panel can be configured (by means of the

configuration tool) to show detection zones and point

information in an alarm situation, or detection zones

only.

Only points in alarm are shown in the display. Faults and

disablements are indicated by LED indicators. The total

number of detection zones in alarm will always be

shown.

By operating the More Events Button, it is possible to

scroll through and view detailed information of the first

64 alarms (or 32 first alarms, if the panel is configured to

show both detection zones and points).

The panel is powered by the detection loop.

Search for products

Back to Top
Product has been added to your cart