Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Autronica Repeater Panel BU-BV-420

Description/Application

The Repeater Panel BU-BV-420 serves as both a Fire

Brigade Panel and an Information Panel.

Settings on a dipswitch determine the type of panel (see

dipswitch settings). The panels communicate with other

system units on the Ethernet-based local area network, AutroNet.

The panel has an 16 x 40-character alphanumeric display.

Fire Brigade Panel

This panel displays alarms and allows you to operate

alarms and receive additional information related to the

relevant operation zone. To operate alarms, a fireman’s

key must be used (access level 2).

The panel is used to silence sounders and to reset alarms

within a defined operation zone.

The panel provides the following buttons:

• More Events button

• Mute Panel button

• Silence Alarms button

• Reset System button

The panels provides the following indicators:

• Fire, More Events, Fire Brig. Signalled, Fault, Function

Disabled, Testing, System Fault, Power

• Internal buzzer

Information Panel

The Information Panel serves as an indication device

only. It provides information related to the defined operation zone(s).

The panel offers the following buttons:

• More Events button for scrolling through several

alarms within the same event window

• Next Window button for stepping to a new event

window, for example from Fire to Fault Warning window.

• Lamp Test button for activating all indicators to be lit for 5 seconds

The panels provides the following indicators:

• Fire / Alarm, Function Disabled, Function Delayed, Testing, Power

• Internal buzzer

Autronica BU-BV-420 Features

Features

• User-friendly display and operator controls

• Scroll function for more alarms

• Backlit operational buttons. Text display suitable for

full darkness operation

• Possible to change to different event windows

• Surface or flush mounting

• Rack mounting in standard 19’’ cabinets and flush

mounting in consoles

• Conforms to CE standards

• Designed to meet IEC 61508 SIL2 requirements,

CEN, EN 54-2. EN 54-4 and EN 54-13 regulations, FM

regulations (Factory Mutual) and the maritime SOLAS

requirements (Safety Of Life At Sea)

The Repeater Panel BU-BV-420 serves as both a Fire

Brigade Panel and an Information Panel.

Settings on a dipswitch determine the type of panel (see

dipswitch settings). The panels communicate with other

system units on the Ethernet-based local area network,

AutroNet.

The panel has an 16 x 40-character alphanumeric display.

Autronica Operator Panel BS-430

Description

BS-430 serves as an operating panel for one or several defined

operation zones.

All alarm handling and system features can be controlled and

monitored from the panel. A restricted scope of operation may

be configured.

The panel communicates with controllers and the entire system

via the Ethernet-based local area network; AutroNet.

The panel is menu operated on a 16-line display, with 40

characters per line.

Indicators

• 16 x 40-character alphanumeric display

• Fire, More Events, Fire Brig. Signalled, Fault, Function

Disabled, Testing, System Fault, Power, Function Delayed,

Alarms Fault, Fire Brig. Fault, Alarms Disabled, Fire Brig.

Disabled, Detector Inhibit, Extinguishing Activated,

Extinguishing Isolated, Local Mode, Dual Safety Stdby,

MultiS SmokeDis

• Internal buzzer

Autronica BS-430 Features

Features

• SelfVerify function for automatic testing of detectors

• Automatic addressing of detectors

• User-friendly display and operator controls

• Backlit operational buttons. Text display suitable for full

darkness operation

• Surface mounting on wall or flush mounting in wall

• Rack mounting in standard 19’’ cabinets and flush mounting

in consoles

• Conforms to CE standards

• Designed to meet IEC 61508 SIL2 requirements,

CEN, EN 54-2. EN 54-4 and EN 54-13 regulations, FM

regulations (Factory Mutual) and the maritime SOLAS

requirements (Safety Of Life At Sea)

Operator Controls

• More Events, Mute Panel, Silence Alarms, Reset System,

Menu, Close Window

• Keyboard with alphanumeric characters and scroll function

• Separate buttons for menu operation (manoeuvre buttons)

• Backlit buttons and text

Autronica Operator Panel BS-430

Description

BS-430 serves as an operating panel for one or several defined

operation zones.

All alarm handling and system features can be controlled and

monitored from the panel. A restricted scope of operation may

be configured.

The panel communicates with controllers and the entire system

via the Ethernet-based local area network; AutroNet.

The panel is menu operated on a 16-line display, with 40

characters per line.

Indicators

• 16 x 40-character alphanumeric display

• Fire, More Events, Fire Brig. Signalled, Fault, Function

Disabled, Testing, System Fault, Power, Function Delayed,

Alarms Fault, Fire Brig. Fault, Alarms Disabled, Fire Brig.

Disabled, Detector Inhibit, Extinguishing Activated,

Extinguishing Isolated, Local Mode, Dual Safety Stdby,

MultiS SmokeDis

• Internal buzzer

Autronica BS-430 Features

Features

• SelfVerify function for automatic testing of detectors

• Automatic addressing of detectors

• User-friendly display and operator controls

• Backlit operational buttons. Text display suitable for full

darkness operation

• Surface mounting on wall or flush mounting in wall

• Rack mounting in standard 19’’ cabinets and flush mounting

in consoles

• Conforms to CE standards

• Designed to meet IEC 61508 SIL2 requirements,

CEN, EN 54-2. EN 54-4 and EN 54-13 regulations, FM

regulations (Factory Mutual) and the maritime SOLAS

requirements (Safety Of Life At Sea)

Operator Controls

• More Events, Mute Panel, Silence Alarms, Reset System,

Menu, Close Window

• Keyboard with alphanumeric characters and scroll function

• Separate buttons for menu operation (manoeuvre buttons)

• Backlit buttons and text

Autronica Controller rack unit BC-440

Features

• Main board of AutroSafe ready for subrack mounting

• Designed to meet the requirements of: – EN54-2  – IACS UR E10

– IMO/SOLAS – FM /NFPA72 – IEC61508 SIL2 (116-BC-440G2 only)

• Subrack 3Ux12HP, 200mm deep

• Fault Output Relay

• Redundant Power Input, monitored

• Serial port RS232/RS422/RS485

• AutroFieldBus

• Redundant Ethernet

Description / Application

The Controller Rack Unit BC-440 serves as a connection unit for

the detection loop, alarm sounders, controls and inputs. It is a

variant of the BC-420 Controller prepared for rack installations.

Together with the IO modules the unit will have the full

functionality of the BC-420 Controller.

The Controller is equipped with 2 Ethernet ports, one

AutroFieldBus port and one serial port. The Controller

communicates with other system units using the Ethernet

based local area network, AutroNet and external equipment

using AutroCom and Modbus.

The serial port may be set to RS-232/422 or 485 and can

communicate with external equipment using AutroCom,

Modbus, NMEA and ESPA 4.4.4.

Autronica BC-440 Features

Features

• Main board of AutroSafe ready for subrack mounting

• Designed to meet the requirements of: – EN54-2  – IACS UR E10

– IMO/SOLAS – FM /NFPA72 – IEC61508 SIL2 (116-BC-440G2 only)

• Subrack 3Ux12HP, 200mm deep

• Fault Output Relay

• Redundant Power Input, monitored

• Serial port RS232/RS422/RS485

• AutroFieldBus

• Redundant Ethernet

Capacity

• 31 BC-440 per system

• 15000 loop units per system

• 30 I/O modules can be connected to one I/O stack if BSL

310A is used (12 I/O modules if BSL-310 is used)

• 12 loop driver modules can be connected to one panel

• 512 loop units can be connected to one I/O-stack

• 1024 loop units can be connected to one panel (a total of

512 detectors and/or manual call points if EN 54 approval is

required)

• 31 AutroFieldBus units can be connected to AutroFieldBus

• 127 loop units can be connected to one detection loop

• 15 loop units can be connected to one Powerloop

Autronica Controller BC-420

Description/Application

The Controller, BC-420. serves as a connection unit for

the detection loop, alarm sounders, controls and inputs.

It can accommodate up to a maximum of 12 modules.

The system offers a Loop Driver Module for detection

loops and several types of I/O modules (see Optional

Modules below).

There can be a maximum of 6 Loop Driver Modules

connected to each Controller. All modules are easily

plugged onto each other on a standard mounting rail

inside the unit.

The Controller provides connections for 2 Ethernet ports

and 2 USB host ports.

The Controller communicates with other system units on

the Ethernet-based local area network, AutroNet.

Optional Modules

• Loop Driver Module (BSD-310/311) for

connection of detection loops

• Output Module (BSB-310) with 4 monitored

outputs

• Output Module (BSJ-310) with 8 open collector

non-monitored outputs

• Input Module (BSE-310) with 4 monitored inputs

• Input Module (BSE-320) with 8 non-monitored

inputs (galvanically isolated)

Indicators

• Power (green)

• Fault (yellow)

Autronica BC-420 Features

Features

• Accommodates up to a maximum of 12 modules, of

which maximum 6 can be Loop Driver Modules

• AutroFieldBus

• Indicators for fault and power

• Surface mounting on wall

• Rack mounting in standard 19’’ cabinets and flush

mounting in consoles

• Conforms to applicable EU directives and regulations

• SIL2 capable according to IEC 61508

• Approved according to CEN Standards EN 54-2. EN

54-4 and EN 54-13. FM regulations (Factory Mutual)

and maritime regulations (IMO/SOLAS and USCG)

Capacity

• 64 system units  on the local area network; AutroNet

• 15000 loop units per system

• 12 modules per fire alarm control panel, of which 6 can

be Loop Driver Modules

• 512 detectors and manual call-points can be

connected to each Fire Alarm Control Panel (EN 54)

• 31 AutroFieldBus units connected to AutroFieldBus

• 127 loop units connected to one detection loop

• 40 socket/loop sounders connected to one detection loop

• 15 loop units connected to one Powerloop

Search for products

Back to Top
Product has been added to your cart