Autronica MIMIC DRIVER BUR-200
Features
1 Mimic Driver is capable of driving 32 current
limited LEDs
1 Mimic Driver is provided with 8 standard
monitored inputs
A maximum of 8 Mimic Drivers can be connected
to the RS-485 Panel Bus, providing a total of 256
outputs and 64 monitored inputs
Powered by 24 VDC, redundant, monitored
Lamp test
LED intensity control
Snap-on to DIN rail (TS-35)
Designed to meet EN 54 and SOLAS
requirements, and conforms to CE standards
Switch Settings Failsafe and line Termination
Master and the last* Slave: The switches S2.1. S2.2
and S2.3 are to be set to ON.
Other Slaves: The switches S2.1. S2.2 and S2.3 are
to be set to OFF.
*Refer to connection Overview – Master/Slave
Drivers.
X2 Panel Bus Address Switch
If S2.7 is set to Master, X2 sets the panel bus
address. If S2.7 is set as a slave, X2 sets the RS
485 daisy-chain slave address. The range for the
switch is 1-9.