Basler Electric BE1-87T Fifth-Harmonic Restraint

Percentage Restraint

A primary concern in differential relay applications is security against high current levels caused by faults

outside the protected zone. Inevitable differences in the saturation characteristics between current

transformers require a compensating decrease in relay sensitivity. It is also necessary to be able to adjust

the sensitivity to compensate for transformer voltage taps or CT mismatches. This is accomplished by

providing a restraint factor proportional to the current flowing through the protected zone (through

current).

BE1-87T relays maintain sensitivity at a specified ratio of trip current to through current. This ratio,

generally referred to as slope, is front-panel adjustable in 5 % increments from 15 to 60 %.

Fifth-Harmonic Restraint

Power transformer overexcitation causes additional exciting current to flow into one set of terminals. This

presents an apparent differential (or operating) current not attributable to an internal fault. Although

potentially damaging, overexcitation is not an internal fault and, therefore, is not an appropriate condition

for transformer differential relay operation. One of the principal components in the complex waveform

produced during overexcitation is the fifth harmonic. BE1-87T relays use fifth-harmonic restraint to inhibit

the differential relay operation.

Basler Electric IFM-150 Control Power (DC+, DC– and AC1. AC2)

Control Power (DC+, DC– and AC1. AC2)

Operating power for the Firing Circuit Chassis is applied to the Control Power inputs. If dc operating power

is used, 125 Vdc should be applied to terminals DC+ and DC–. If ac operating power is used, 120 Vac

should be applied to terminals AC1 and AC2. Both inputs may be used if redundant control power is desired.

Bridge Control Voltage (COM, VC+)

This signal determines the firing control angle of the rectifier bridge SCRs. The Bridge Control Voltage

Input accepts a voltage range of –10 to +10 Vdc. The DECS must be programmed to supply the same

range of control voltage. Refer to Basler publication 9369700990 for information about DECS-400

configuration and Basler publication 9597100990 for information about DECS-450 configuration.

Basler Electric IFM-150 Terminal Voltage Limiter Active Relay

Start/Stop (FS+, FS–)

A contact closure at this input initiates sampling of the synchronizing voltage (to determine phase

rotation) and calculation of the pulse generation time delay. Opening this contact input terminates the

firing pulses.

Terminal Voltage Limiter Enable (VTLIM+, VTLIM–)

The terminal voltage limiter is enabled when contact closure is sensed at this input. When enabled, the

terminal limiter will prevent the generator voltage from exceeding the limiter reference level.

Outputs

The following paragraphs describe the function of the IFM-150 outputs.

Firing Pulses

These outputs supply firing pulses to the gate trigger inputs of the Rectifier Chassis. The firing pulse

terminals used depend on the model of IFM-150. Installation illustrates typical firing pulse output

connections for single-phase and three-phase rectifier chassis applications.

Watchdog Relay (WTCHDG1. WTCHDG2)

The Watchdog Relay output closes to indicate a software execution problem within the IFM-150 or a loss

of power supply. This output remains closed for several seconds after the application of control power.

Alarm Relay (ALRM1. ALRM2)

The Alarm Relay output closes when the monitored synchronizing transformer frequency decreases

below the programmable level of the BESTCOMS Safe Mode Frequency setting. The output opens when

the frequency increases to 1 hertz above the Safe Mode Frequency setting. This output is disabled when

the Start/Stop contact input (FS+, FS–) is open.

Terminal Voltage Limiter Active Relay (LIMACTV1. LIMACTV2)

The normally-open Terminal Voltage Limiter Active Relay output closes when the terminal voltage limiter

activates due to high generator voltage. When the generator voltage decreases below the limiter

reference level, the terminal voltage limiter deactivates and the Terminal Voltage Limiter Active Relay

output opens.

Basler Electric IFM-150 Interface Firing Module

Introduction

The Basler Electric IFM-150 Interface Firing Module receives a control signal from a DECS-400 or DECS

450 Digital Excitation Control System and calculates a phase-control firing angle that is synchronized with

the power transformer output. The IFM-150 then generates output pulses to drive the SCRs of an

excitation rectifier chassis.

The IFM-150 is available in two configurations that control either a single-phase rectifier module or a

three-phase rectifier chassis.

Three-phase IFM-150 modules can be user-configured to supply SCR firing pulses to a fully controlled or

half controlled (positive or negative) rectifier bridge. A fully controlled rectifier bridge requires that the IFM

150 supply six sets of firing pulses to drive the SCRs of the bridge. A half controlled rectifier bridge

contains three SCRs and three diodes. Positive control is used when the SCRs are connected to the

positive side (F+) of the field output. Negative control is used when the SCRs are connected to the

negative side (F–) of the field output.

A single-phase IFM-150 provides full control of a single-phase rectifier module. Four sets of firing pulses

are generated by the IFM-150 to drive the rectifier module SCRs.

Basler Electric BE1-87T Transformer Differential Relay

Second-Harmonic Restraint

Magnetizing inrush current presents another problem unique to transformer differential relays. Relays

must be capable of detecting the small differences in current caused by the shorting of a limited number

of turns, yet remain secure against the occurrence of magnetizing currents many times the transformer

rating (as seen at one set of terminals).

Although magnetizing inrush is usually associated with the energizing of the transformer, any abrupt

change in the energizing voltage may produce this phenomenon. Common causes are the transients

generated during the onset, evolution and removal of external faults. Desensitizing the relay only during

energization is therefore insufficient.

Magnetizing inrush produces an offset sine wave rich in all harmonics. BE1-87T relays use the second

harmonic to restrain operation because it predominates and because it does not occur in significant

magnitude or duration at other times.

Three-phase BE1-87T relays use second-harmonic sharing. The second-harmonic content of all three

phases is summed together to derive the restraint for each phase. As a result, the second-harmonic

inhibit range and the associated factory setting, is higher than on single-phase relays.

Basler Electric BE1-87T Three-Phase relays can provide zero-sequence filtering

Single-Phase

BE1-87T Single-Phase relays require phase angle compensation to be accomplished externally by proper

connection of the system CT secondaries. A wye/delta transformer requires that the CT secondaries be

connected in delta for the wye winding and in wye for the delta winding. This type of connection also

eliminates the zero-sequence component of current which could cause a false trip (operation) during

external ground fault conditions on the wye system.

Three-Phase

BE1-87T Three-Phase relays can provide zero-sequence filtering and compensation for phase shifts

introduced by the connections of the power transformer. This 30° Phase Shift compensation (either ±30°

or no compensation) is field selectable. Additionally, this feature allows sharing the transformer differential

relay CTs with other relays or instrumentation.

BE1-87T relays use the highest input current (in per unit values) to operate on maximum restraint. The

relay does not have a conventional operate winding in the internal magnetics. Operating current is

developed within the electronics of the relay.

Unrestrained Trip

Severe internal transformer faults may cause CT saturation. Under such circumstances, harmonic

restraint transformer differential relays may fail to trip because of the extremely high harmonic content in

the waveform. Lack of operation can result in severe transformer damage.

BE1-87T relays provide an independent unrestrained tripping function. When set above the possible

inrush current magnitude, this function provides high-speed protection for the most severe internal faults.

Basler Electric BE1-87T APPLICATION

APPLICATION

In general, power transformers have different values of current flowing through their primary, secondary,

and tertiary windings. These currents have specific phase relationships depending upon the connections

of the individual windings (e.g., wye/delta). As inputs to a differential relay, these currents must be

compensated or scaled so that the relay can compare the inputs and determine when an unbalance

exists. Under ideal operating conditions, the scaled vector sum of these currents is zero.

Because it is practically impossible to match the magnitudes of these detected currents from the various

power windings using standard CT ratios, the currents are matched within the relay by scaling each of the

applied currents by an appropriate factor called a Tap Setting. This is set by means of the front panel

INPUT dials. By selecting suitable tap ratios, the applied currents are scaled within the relay to achieve

the desired balance for normal operating conditions. BE1-87T relays offer a range of available tap settings

for inputs between 0.4 A to 1.78 A (Sensing Input Range Options 2 and 4 for a 1 A CT) or 2.0 to 8.9 A

(Sensing Input Range Options 1 and 3 for a 5 A CT). These settings are independently adjustable in

increments of 0.02 A for Sensing Input Range Options 2 and 4. or 0.1 A for Sensing Input Range Options

1 and 3. These small increments allow more precise scaling of the applied currents and usually eliminate

the need for installing auxiliary ratio-matching CTs.

Aerotech Automation1 XI4 Feedback Features

Feedback Features

Each axis on the XI4 includes encoder feedback inputs so that you can

control axis position very accurately. This input accepts incremental

square-wave and absolute (optional) feedback devices.

The dedicated axis feedback signals include encoder feedback

(sine +/-, cosine +/- & marker inputs), 2x end of travel (EOT) limit switch

inputs and amplifier enable and fault I/O. A dedicated digital I/O port

supports 8 digital inputs, 8 digital outputs (sourcing or sinking),

1 differential high-speed input and a dedicated high-speed PSO output.

Platform Power

More than just hardware, the XI4 gives you access to the complete power

of the Automation1 motion control platform. This includes the Automation1

motion development kit (MDK), the intelligent software-based controller

(iSMC) and the powerful AeroScript™ programming language with

integrated RS-274 G and M code support. The Automation1 iSMC can also

be programmed by various controller APIs, which provide flexible methods

of integrating the XI4 and the axes it controls into your system architecture.

Basler Electric BE1-87T Transformer Differential Relays

DESCRIPTION

BE1-87T Transformer Differential Relays provide primary protection for power transformers and are

available in either Single-Phase or Three-Phase configurations. The solid-state BE1-87T compares the

currents entering and leaving the protected transformer. If a fault is detected, the relay initiates a trip

signal to isolate the power transformer. This limits damage to the transformer and minimizes the impact

on the power system.

BE1-87T relays use three types of restraint:

• Percentage of through-current

• Second harmonic

• Fifth harmonic

Selectivity in differential relaying is based on the ability to distinguish between internal and external faults.

This is achieved by comparing the currents into and out of a power transformer. Comparing these

currents often requires more than two inputs. For example:

• Power transformers may have a significant portion (greater than 10 %) of the current flowing in a

third or tertiary winding.

• Power transformers can have multiple breakers for a given winding (e.g., ring bus or breaker

and-a-half bus).

BE1-87T relays are available with up to five restraint inputs for the single-phase unit and up to three

restraint inputs per phase for the three-phase unit.

Aerotech Automation1 iXI4 KEY FEATURES

Automation1

The iXI4 is a part of the user-friendly Automation1 motion control

platform, which includes the following:

• Development Software

• Controls

• Motor Drives

• Fiber-Optic HyperWire® Communication Busi

KEY FEATURES:

• Unlocks the full MOTION CONTROL power of our Automation1

-iSMC intelligent software based motion controller

• Features COMPLETE CONFIGURATION &PERFORMANCE

capability of the XI4 servo controller

• CONNECT TO THE CONTROLLER using Modbus TCP/IP or

TCP Socket interface

• Enables up to 12 AXES OF CONTROL when more Automation1

drives are connected over the HyperWire fiber-optic bus

• Includes up to four SINGLE CONNECTOR axis interface connectors

• Features up to four axes of 20 kHz CLOSED LOOP SERVO control

Search for products

Back to Top
Product has been added to your cart